SELECT
MENU
STATIC TRANSFER SWITCH
ON/OFF
STATUS
ETHERNET
AC OUTPUT
UTILITY
PRIMARY
INVERTER
PRIMARY
Network Activity
Network Link
Indicator LED of
System Status.
Data output to monitor
the system status over
an Ethernet based
network.
Turn the Inverter
Modules on or off.
Disconnect will remove
the AC Voltage output
from the system.
10/100 BASE T
Voltage Transfer Set Point ( 120Vac )
Low voltage settings: 100Vac
High voltage settings: 130Vac
Features
Alarm Conditions
Load on alternate
Inverter alarms (if equipped)
Fast AC Failure Detection (< 2 ms)
Primary selection via front panel switch
Optional generator start
Solid State
Zero Switching time
Modular Design
Single phase in 5, 10, 20KW
Split phase in 10, 20, 40KW
3 Phase 15, 30, 60KW
SNMP Monitoring
AC Amps
AC Volts
DC Amps
DC Volts
MX SOLID STATE TRANSFER SWITCH
Page 10
Operation
The Exeltech Solid State Transfer Switch
sets a new standard in power density and
alarm capabilities. Its modular design is
available in 3 power levels, 5, 10 and 20KW,
which can be linked together to provide single,
split, and 3 phase systems. The Switches can
communicate on a SNMP protocol via TCP/IP
that provides data on AC volts and amps of
both the primary and secondary sources. If
linked to an MX inverter system it will perform
all the normal functions of the required alarm
card plus communicate DC volts and amps,
all inverter alarms including inverter fail, module
fail, and over temperature. If the inverter is so
equipped, the switch will report both DC Bus
A and Bus B Voltage. Additionally, the switch
can report combined Major and Minor alarms
via SNMP and form C contacts. The minor
.
alarm is triggered with any alarm, the major alarm is only triggered with complete loss of AC Voltage to the load or when a
complete loss is imminent.
All good to good transfers are synchronous and performed at zero crossing. The switch will operate on the user selectable
primary source until the primary source fails or operates out of limits. It will switch to the secondary source in less than 4 ms
worst case. If the primary returns to normal limits, the switch will wait 15 sec for stabilization, monitor the primary and
secondary source, upon assuring they are in phase, it will switch at the next available zero crossing.
The status of all available alarms, status, and measurements are available via a 2 X 8 LCD display. It is highly
recommended that an Exeltech maintenance bypass switch be used in conjunction with this or any other solid state transfer
switch. This switch can be used with Exeltech inverters or between any 2 AC Sources whether they be inverters, generators
or utility sources.
.
.
.