XP125 INSTALLATION AND OPERATION MANUAL
Page 11
APPENDIX A
XP-125 / 12VDC
13.8 VDC
10.4 / 10.6 VDC
16.5 VDC
12.3 A 13.9 A
XP-125 / 24VDC
27.6 VDC
19 / 21 VDC
33 VDC
6.1 A 7 A
XP-125 / 48VDC
55.2 VDC
41.5 / 42.5 VDC
62 VDC
3.1 A 3.5 A
XP-125 / 66VDC
75.9 VDC
57.5 / 58.5 VDC
91 VDC
2.2 A 2.5 A
XP-125 / 108VDC
124.0 VDC
94 / 95 VDC
149 VDC
1.4 A 1.6 A
MODEL
NORMAL
VDC
MINIMUM VDC
CUT-OFF / ALARM
MAXIMUM
VDC
RATED
CURRENT
PEAK
CURRENT
XP-125 / 12VDC
MODEL
Input Power Requirements:
Recommended Input Wire Sizes (For Variable Distances from the Battery):
10 AWG
LESS THAN 5’
8 AWG
LESS THAN 10’
6 AWG
LESS THAN 15’
4 AWG
LESS THAN 20’
XP-125 / 24VDC 16 AWG 12 AWG 12 AWG 10 AWG
XP-125 / 48VDC 18 AWG 18 AWG 18 AWG 16 AWG
XP-125 / 66VDC 18 AWG 18 AWG 18 AWG 18 AWG
XP-125 / 108VDC 18 AWG 18 AWG 18 AWG 18 AWG
Note: The table specifies standard wire sizes (not smaller than 18 AWG) that will provide less than a
2% voltage drop at Low-line Input voltage and Rated Output Power.
0
7.900”
0
2.154”
0
.250”
4.529”
4.779”
0
.250”
7.650”
7.900”
.156” DIA. 4 PLACES
0
4.929”
0
2.154”
XP-125 Mechanical Specifications:
TOP
FRONT SIDE
020-00131-100 PNT BRKT XP125 MOUNTING (2/4)